Ventilation
These dehumidifiers are suitable for operation in the environments that require state-of-the-art control of both parameters, such as swimming pools, food storages, salami and cheese making shops or any other premises where humidity control is essential so that the goods do not get spoiled.
It allows humidity control through a hygrostat (dry contact) on board
or remote installation.ьThe fan speed is fixed or controlled by a potentiometer.
For three-phase units a phase monitor is included.
Available inputs/outputs
*3, 4 Including condensate tray and insulation.
* It is possible to install only one water coil; for size up to 0300, on/off three-ways valve.
WINTER: start up, no occupants, covered pool, heating with hot water coil.
Compressor: OFF
Hot water coil: ON (optional)
Desuperheater: OFF (optional)
Remote condenser: OFF (MST models)
WINTER: normal operation, pool open, dehumidification.
Compressor: ON
Hot water coil: OFF (optional)
Desuperheater: OFF (optional)
Remote condenser: OFF (MST models)
SPRING, AUTUMN: normal operation, pool open, dehumidification with heat recovery (desuperheater)
Compressor: ON
Hot water coil: OFF (optional)
Desuperheater: ON (optional)
Remote condenser: OFF (MST models)
SUMMER: normal operation, pool open, dehumidification and cooling (remote condenser)
Compressor: ON
Hot water coil: OFF (optional)
Desuperheater: OFF (optional)
Remote condenser: ON (mST models)
Specifications | Units | MIT - MST 010 |
MIT - MST 013 |
MIT - MST 016 |
MIT - MST 019 |
MIT - MST 021 |
MIT - MST 026 |
MIT - MST 030 |
MIT - MST 035 |
MIT - MST 045 |
MIT - MST 058 |
Dehumidification capacity | l/day | 100 | 128 | 157 | 190 | 210 | 268 | 302 | 358 | 452 | 581 |
Air flow rate |
m3/h |
900 | 1200 | 1600 | 1600 | 2000 | 2800 | 2800 | 3800 | 4000 | 4800 |
Cooling capacity | kW | 4,9 | 6,5 | 8 | 10 | 11 | 15 | 16 | 19 | 23 | 30 |
Water heater capacity | kW | 5,5 | 9,8 | 9,8 | 9,8 | 16,5 | 17 | 17 | 26,5 | 26,5 | 27 |
Electric heater capacity | kW | upon request | |||||||||
Power supply | V/phases / Hz | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
Dimensions (WxLxH) | mm | 700х550х 1100 |
700х550х900 | 700х850х900 | 830х850х1350 |
Specifications | Units | MIT - MST 075 |
MIT - MST 095 |
MIT - MST 110 |
MIT - MST 140 |
MIT - MST 150 |
MIT - MST 170 |
MIT - MST 190 |
MIT - MST 220 |
MIT - MST 300 |
MIT - MST 450 |
Dehumidification capacity | l/day | 760 | 955 | 1120 | 1380 | 1480 | 1710 | 1870 | 2180 | 2960 | 4650 |
Air flow rate |
m3/h |
7000 | 8200 | 11000 | 12500 | 13000 | 15000 | 15000 | 17000 | 25000 | 3500 |
Cooling capacity | kW | 38 | 50 | 56 | 66 | 75 | 86 | 96 | 110 | 148 | 226 |
Water heater capacity | kW | 48 | 55 | 76 | 83 | 98 | 107 | 107 | 118 | 168 | 235 |
Electric heater capacity | kW | upon request | |||||||||
Power supply | V / phases / Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3+N/50 |
Dimensions (WxLxH) | mm | 1000х1400х1350 | 1000х1950х1640 | 1000x2500x1640 | 1000х3390х 1640 |
1000x4430x 2600 |
All the data refer to: air temperature 30 °C, relative humidity 80%, water temperature 80/70 °C
Note:
MIT – standard (industrial) version
MST – pool water version