GTranslate
English French German Greek Italian Portuguese Russian Spanish

Medium ESP duct fan coil units HPL series

These medium-pressure ductable fan coil units are designed to supply air via long pipelines, and support both horizontal and vertical installation. The units are suitable for residential houses, offices, educational and shopping malls
Medium ESP duct fan coil units HPL series

The fan coil has 7 standard sizes of different air flow capacities (from 340 to 2100 m3/h), each of which is equipped with a 3- or 4-row coil and with the possibility of adding a 1- or 2-row coil for 4-pipe systems. This is the most complete range, ideal for all air conditioning requirements.

2,93 ... 11,29 kW
Cooling capacity :
3,31 ... 13,13 kW
Heating capacity :
Key features :
Key features :
  • High level of comfort
  • Wide operating range
  • Static pressure up to 80 Pa
  • Galvanized steel casing
  • High-efficiency copper heat exchanger
  • Statically and dynamically balanced fan for extremely quiet operation
  • Installation in horizontal and vertical position
Advantages :
Advantages :
  • The casing is made of 1mm galvanized steel and insulated with 3mm polyolefin foam (class M1).
  • Fans have aluminium or plastic blades directly keyed on the motor.
  • The 5-speed motor is mounted on anti-vibration pads. The design features internal thermal protection with auto reset (protection rating IP 20, class B).
  • The heat exchanger is not suitable for use in corrosive atmosphere where it may be subject  to corrosion. The connections are on the left hand side looking from the air outlet of the unit. 
  • The condensate tray is made of plastic. The L-shaped design allows installing the fan coil unit in either horizontal or vertical position.
  • The filter is made of polypropylene fiber stretched on a galvanized steel frame. The frame is installed into special guides for easy filter removal and installation during maintenance.
Fan coil thermostat Mycond Block
Fan coil thermostat Mycond  TRF-B2 white /black
The optimal set of automation for affordable and simple control by smartphone

 

3-row fan coil units, 2-pipe models. Specifications

 

Specifications

 

Units HPL 13 HPL 23 HPL 33 HPL 43 HPL 53 HPL 63 HPL 73
Air flow m3/h 535 860 1115 1340 1375 1635 2100
Cooling capacity kW 2,93 4,47 6 6,74 7,24 8,56 9,89
Heating capacity kW 3,31 5,18 6,99 8,11 8,38 9,5 11,54
Motor power input W 55 110 126 175 174 166 245
Sound power (Lw) dB(A) 51 55 57 63 62 61 66
Inlet/outlet water pipe   1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
Condensate pipe mm DN15 DN15 DN15 DN15 DN15 DN15 DN15

4-row fan coil units, 2-pipe models. Specifications  

 

Specifications Units HPL 14 HPL 24 HPL 34 HPL 44 HPL 54 HPL 64 HPL 74
Air flow m3/h 535 860 1115 1340 1375 1635 2100
Cooling capacity kW 3,37 5,45 6,95 7,42 8,01 9,55 11,29
Heating capacity kW 3,6 5,76 7,32 8,57 8,84 10,62 13,13
Motor power input W 55 110 126 175 174 166 245
Sound power (Lw) dB(A) 51 55 57 63 62 61 66
Inlet/outlet water pipe   1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
Condensate pipe mm DN15 DN15 DN15 DN15 DN15 DN15 DN15

3+1-row fan coil unit, 4-pipe models.Specifications  

 

Specifications Units HPL 13-4T/1R HPL 23-4T/1R HPL 33-4T/1R HPL 43-4T/1R HPL 53-4T/1R HPL 63-4T/1R HPL 73-4T/1R
Air flow m3/h 535 860 1115 1340 1375 1635 2100
Cooling capacity kW 2,93 4,47 6 6,74 7,24 8,56 9,89
Heating capacity kW 2,5 3,7 4,87 5,48 5,79 6,93 8,12
Motor power input W 55 110 126 175 174 166 245
Sound power (Lw) dB(A) 51 55 57 63 62 61 66
Inlet/outlet water pipe   1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
Condensate pipe mm DN15 DN15 DN15 DN15 DN15 DN15 DN15

 

The characteristics are given for the following operating parameters:
Static pressure: 0Pa
COOLING: inlet air temperature +27 °C dry. temperature, +19 °C humidity. therm. Inlet/outlet water temperature. +7/12 °C.
HEATING: air temperature at the entrance is +20 °C. Inlet/outlet water temperature. +50/45 °C.
Heating 4-pipe system: air temperature at the entrance +20 °C. Inlet/outlet water temperature. +65/55 °C.

Vertical installation
Vertical installation

Note:
(*) — Coil connections on the left
(**) — Additional condensate tray (option)
(***) — Intake frame dimensions: E x 119 mm
(****) — External diameter

Horizontal installation
Horizontal installation

Note:
(*) — Coil connections on the left
(**) — Additional condensate tray (option)
(***) — Intake frame dimensions: E x 119 mm
(****) — External diameter

 

 

Model Units HPL 1 HPL 2 HPL 3 HPL 4 HPL 5 HPL 6 HPL 7
D mm 689 904 1119 1119 1334 1549 1549
E mm 645 860 1075 1075 1290 1505 1505
F mm 669 884 1099 1099 1314 1529 1529
Coil connections
3- or 4-row coils / Additional heating coil (1 or 2 rows)
Coil connections
Model Units HPL 1 HPL 2 HPL 3 HPL 4 HPL 5 HPL 6 HPL 7
3 rows kg 18,5 25,4 26,5 27,9 38,4 47,2 47,4
3+1 rows kg 19,7 26,9 28,3 29,7 40,3 49,5 49,7
4 rows kg 19,5 26,7 27,9 29,0 39,8 48,9 49,1

 

 

 

    
Want to buy

Feedback form

Invitation to cooperation
Expert AI