Ventilation
Wide power range. The fan coil unit has the function of cooling, heating and ventilation. Designed to maintain comfortable conditions in the premises of a residential building, office, commercial premises, etc.
Specifications | Units | MCFC-034 | MCFC-051 | MCFC-068 | MCFC-085 | MCFC-102 | |
Air flow rate, high / medium / low. | m3/h | 340/255/170 | 510/382/255 | 680/510/340 | 850/638/425 | 1020/765/510 | |
Cooling capacity, high / medium / low. | W | 1800/1440/1170 | 2700/2160/1755 | 3600/2880/2340 | 4500/3600/2925 | 5400/4320/3510 | |
Heating capacity, high / medium / low. | W | 2700/2160/1755 | 4050/3240/2633 | 5400/4320/3510 | 6750/5400/4388 | 8100/6480/5265 | |
External static pressure | Pa. | 50 | 50 | 50 | 50 | 50 | |
Noise level | dB(A) | 42 | 44 | 46 | 47 | 49 | |
Water consumption | m3/h | 0,39 | 0,55 | 0,7 | 0,82 | 0,91 | |
Drop in water pressure | kPa | 12 | 16 | 20 | 23 | 26 | |
Number of fans | 1 | 2 | 2 | 2 | 2 | ||
Fan motor | Number of engines | 1 | 1 | 1 | 1 | 1 | |
Low speed | W | 49 | 66 | 84 | 100 | 118 | |
Maximum working pressure | MPa | 1,6 | 1,6 | 1,6 | 1,6 | 1,6 | |
Inlet / outlet water pipe | mm | Rc3/4”(DN20) | Rc3/4”(DN20) | Rc3/4”(DN20) | Rc3/4”(DN20) | Rc3/4”(DN20) | |
Drain pipe | mm | R3/4”(DN20) | R3/4”(DN20) | R3/4”(DN20) | R3/4”(DN20) | R3/4”(DN20) | |
Net weight | kg | 17 | 19 | 20 | 22 | 25 |
Specifications | Units | MCFC-136 | MCFC-170 | MCFC-204 | MCFC-238 | |
Air flow rate, high / medium / low. | m3/h | 1360/1020/680 | 1700/1275/850 | 2040/1530/1020 | 2380/1785/1190 | |
Cooling capacity, high / medium / low. | W | 7200/5760/4680 | 9000/7200/5850 | 10800/8640/7020 | 12600/10080/8190 | |
Heating capacity, high / medium / low. | W | 10800/8640/7020 | 13500/10800/8775 | 16200/12960/10530 | 18900/15120/12285 | |
External static pressure | Pa. | 50 | 50 | 50 | 50 | |
Noise level | dB(A) | 50 | 52 | 54 | 56 | |
Water consumption | m3/h | 1,34 | 1,59 | 1,8 | 2,07 | |
Drop in water pressure | kPa | 40 | 40 | 40 | 50 | |
Number of fans | 3 | 4 | 4 | 4 | ||
Fan motor | Number of engines | 1 | 1 | 1 | 1 | |
Low speed | W | 174 | 210 | 250 | 300 | |
Maximum working pressure | MPa | 1,6 | 1,6 | 1,6 | 1,6 | |
Inlet / outlet water pipe | mm | Rc3/4”(DN20) | Rc3/4”(Ду20) | Rc3/4”(DN20) | Rc3/4”(DN20) | |
Трубка для конденсату | mm | R3/4”(DN20) | R3/4”(DN20) | R3/4”(DN20) | R3/4”(DN20) | |
Net weight | kg | 31 | 37 | 42 | 44 |
Note.
1. The cooling capacity was tested under the following conditions: inlet air temperature 27°C dry bulb / 19.5°C wet
bulb; inlet/outlet water temperature 7°C / 12°C.
2. The heat output was tested under the following conditions: inlet air temperature 21°C dry thermometer; inlet
water temperature 60/50°C.
3. The noise level was tested in a completely echo-free room.
4. These performance and flow rates are given at a static pressure of 30Pa.
Model | Units | MCFC-034 | MCFC-051 | MCFC-068 | MCFC-085 | MCFC-102 | MCFC-136 | MCFC-170 | MCFC-204 | MCFC-238 |
A | мм | 510 | 640 | 745 | 830 | 960 | 1260 | 1410 | 1630 | 1830 |
B | мм | 480 | 610 | 715 | 800 | 930 | 1230 | 1380 | 1600 | 1800 |
C | мм | 693 | 823 | 928 | 1013 | 1143 | 1443 | 1593 | 1813 | 2013 |
Model | Units | MCFC-034 | MCFC-051 | MCFC-068 | MCFC-085 | MCFC-102 | MCFC-136 | MCFC-170 | MCFC-204 | MCFC-238 |
A | мм | 510 | 640 | 745 | 830 | 960 | 1260 | 1410 | 1630 | 1830 |
B | мм | 480 | 610 | 715 | 800 | 930 | 1230 | 1380 | 1600 | 1800 |
C | мм | 693 | 823 | 928 | 1013 | 1143 | 1443 | 1593 | 1813 | 2013 |
D | мм | 420 | 540 | 680 | 740 | 860 | 1060 | 1320 | 1520 | 1660 |