The cassette fan coil unit is installed on the ceiling, thereby not taking up valuable space on the walls and without disturbing the interior design. This type is most often used in commercial spaces with not too high ceiling
4-way cassette <br/>fan coil units <br/>MCFK-T2 series

A wide range of cooling and heating capacities allows them to be used for spaces of any size. And the elegant stylish design of decoration panel will suit any interior.

2.4 ... 12.6 kW
Cooling capacity :
3,7 ... 18,9 kW
Heating capacity :
Features and advantages :

Wireless remote control

Features and advantages :
  • Uses the room space with maximum benefit due to small size
  • 4-way air distribution system allows you to evenly cool or heat the room without creating drafts and discomfort
  • Revolutionary centrifugal fan design ensures quiet operation and high airflow
  • Optimized heat exchanger provides high cooling and heating efficiency

Panel

  • Powerful drainage pump provides a water head up to 1200 mm
  • High efficiency washable filter with a removable filtering element made of synthetic fiber for even fresher and cleaner air 
  • Fresh air intake port
  • IR remote control unit has simple programming with easy to read buttons for control. Comfortable and lightweight design that makes it perfect for daily use

Specifications Units MCFK-03T2 MCFK-04T2 MCFK-05T2 MCFK-06T2
Air flow rate, H/M/L

m3/h

510/440/360 680/580/480 850/730/600 1020/765/510
Total cooling capacity, H/M/L kW 3,3/2,8/2,4 3,9/3,4/2,8 4,5/3,6/3,1 5,4/4,6/3,5
Heating capacity, H/M/L kW 4,8/4,2/3,7 5,8/5,1/4,5 6,8/5,9/5,2 8,1/6,9/5,3
Operating current A 0,23 0,27 0,31 0,41
Noise level dB(A) 39 42 44 44
Water flow rate kg/h 620 700 940 1150
Pressure drop in the heat exchanger kPa 26 27 29 31
Fan/motor type   Centrifugal fan / capacitor start-and-run motor
Insulation   Class B Class B Class B Class B
Power supply   220-230 V / 1 phase / 50 or 60 Hz
Motor power consumption W 55 62 75 90
Heat exchanger   Copper pipes with aluminium fins, 2 rows
Max. operating pressure MPa 1,6 1,6 1,6 1,6
Inlet/outlet water pipe mm DN20, 3/4” DN20, 3/4” DN20, 3/4” DN20, 3/4”
Condensate pipe mm DN20, 3/4” DN20, 3/4” DN20, 3/4” DN20, 3/4”
Unit dimensions mm 570x570x260 570x570x260 570x570x260 835x835x240
Panel dimensions mm 650x650x55 650x650x55 650x650x55 950x950x55
Packed unit dimensions mm 650x650x290 650x650x290 650x650x290 910x910x310
Packed panel dimensions mm 710x710x80 710x710x80 710x710x80 1000x1000x100
Net weight, unit kg 18 18 18 24
Net weight, panel kg 3 3 3 5
Packed unit weight kg 20,3 20,3 20,3 28
Packed panel weight kg 5 5 5 7

 

Specifications Units MCFK-08T2 MCFK-10T2 MCFK-12T2 MCFK-14T2
Air flow rate, H/M/L

m3/h

1360/1020/680 1700/1275/850 2040/1530/1020 2380/1785/1190
Total cooling capacity, H/M/L kW 7,2/6,2/4,7 9,1/7,7/5,9 10,8/9,2/7,1 12,6/10,7/8,2
Heating capacity, H/M/L kW 10,8/9,2/7,0 13,5/11,5/8,8 16,2/13,8/10,5 18,9/16,1/12,3
Operating current A 0,59 0,67 0,84 0,98
Noise level dB(A) 45 48 50 51
Water flow rate kg/h 1400 1680 1820 2245
Pressure drop in the heat exchanger kPa 34 36 39 42
Fan/motor type   Centrifugal fan / capacitor start-and-run motor
Insulation   Class B Class B Class B Class B
Power supply   220-230 V / 1 phase / 50 or 60 Hz
Motor power consumption W 131 145 186 225
Heat exchanger   Copper pipes with aluminium fins, 2 rows
Max. operating pressure MPa 1,6 1,6 1,6 1,6
Inlet/outlet water pipe mm DN20, 3/4” DN20, 3/4” DN20, 3/4” DN20, 3/4”
Condensate pipe mm DN20, 3/4” DN20, 3/4” DN20, 3/4” DN20, 3/4”
Unit dimensions mm 835x835x240 835x835x280 835x835x280 835x835x280
Panel dimensions mm 950x950x55 950x950x55 950x950x55 950x950x55
Packed unit dimensions mm 910x910x310 910x910x350 910x910x350 910x910x350
Packed panel dimensions mm 1000x1000x100 1000x1000x100 1000x1000x100 1000x1000x100
Net weight, unit kg 25,5 26,5 28 28
Net weight, panel kg 5 5 5 5
Packed unit weight kg 29 31 32,5 32,5
Packed panel weight kg 7 7 7 7

Rated test conditions:
Cooling: inlet air temperature +27 °C DB / +19.5 °C WB, inlet water temperature +7 °C, outlet water temperature +12 °C.
Heating: inlet air temperature +21 °C, inlet water temperature +60 °C, the same water flow rate as in the cooling mode.
Sound pressure level has been measured in a sound insulated room, with a reference point at 1.5 m below the vertical axis of the unit.

 

Dimensions
Appearance and dimensions of fan coil units MCFK 03\04\05
Dimensions
Dimensions
Appearance and dimensions of fan coil units MCFK 06/08
Dimensions
Dimensions
Appearance and dimensions of fan coil units MCFK 10/12/14
Dimensions
Components*
 Components*

Legend:

1 – Decorative grille with a filter
2 – Air flow adjustment panel
3 – Drainage pan
4 – Heat exchanger
5 – Control box
6 – Foam frame
7 – Main body
8 – Pipe fixture
9 – Fan motor
10 – Drainage pump
11 – Fan

* The components may vary depending on the model. This schematic drawing refers to models MCFK 10/12/14.

 

 

 

    